CMS 10kVA UPS, Scalable to 100kVA, 400V, 64pcs Battery

CMS 10kVA UPS, Scalable to 100kVA, 400V, 64pcs Battery
CMS 10kVA UPS, Scalable to 100kVA, 400V, 64pcs Battery

The CMS 10kVA UPS is one of our modular UPS systems. It is a suitable solution for small or medium-sized power required projects. The CMS 10kVA UPS has a compact structure (floor area 0.48㎡), reliable performance and necessary redundancy. Each module has a power of 10kVA and can be upgraded to 50kVA or 100kVA UPS systems according to your specific circumstances.

CMS-50/10 UPS System
  • Maximum power:50kVA
  • Power module model:CM10
  • Module power:10kVA
  • Direct voltage: ±384V
  • Dimension: 600*800*1200mm (W*D*H), standard 19 inch cabinet
  • Weight: 120kg
CMS-100/10 UPS System
  • Maximum power:100kVA
  • Power module model:CM10
  • Module power:10kVA
  • Direct voltage: ±384V
  • Dimension: 600*800*1600 mm (W*D*H), standard 19 inch cabinet
  • Weight: 150kg
UPS System Technical Parameters
Module
Module model CM10
Module power 10kVA
Rated input voltage ±384VDC
Power connection 3/3 phase
Module dimension (W*D*H)mm 482×465×89
Weight (kg) Approximate 16 kg
Module charging Each module provides 2.5kW charging power
Input power factor ≥0.99
Overload ability Exceeds system overload requirements
Maximum heat dissipation power 475w
THDI (%) ≤3%
Mains Input
Input mode 3-phase +N +E, 1-phase +N +E
Input voltage 380V/220V±20%, 400V/230V±20%, 415V/240V±20%
Input frequency 50Hz±10%, 60Hz±10%
Power woke-in (Sec.) 60sec
THDI (%) <3%
Input PF ≥0.99
Bypass Input
Input voltage 380V/220V±20%, 400V/230V±20%, 415V/240V±20%
Input frequency 50 Hz, 60 Hz
Range of Frequency Synchro 50 Hz±4%, 60 Hz±4%
DC Input
Rated Input voltage ±384VDC
Input voltage tolerance ±345V~±440V DC
Battery Charging
Charging current limited yes
Charging ability 10 hours (2 hours back up)
Stability of charging voltage ±1%
AC Output
UPS power factor 1
Output voltage 380V/220V AC, 400V/230V AC, 415V/240V AC
Output frequency ±4%;±0.2% (battery supply)
Output voltage stability ±1%
Output voltage recovering time <20ms (load 0~100% change)
Overload ability Operate 10mins with 125% load
Transfer from mains to battery supply 0ms
Transfer from bypass to inverter supply < 1ms
Peak factor 3:01
Waveform distortion ≤1% ( linear load ), ≤3%( non-linear load )
Overall efficiency ≥95% (AC~AC), ≥98% (DC~AC)
Load share precision ≤5%
Operation Environment
Ambient temperature -25℃~60℃
Operating temperature -5℃~40℃
Maximum operation altitude ≤1500m
Relative humidity ≤95% non-cadency
Protection degree IP30
Cooling Air cooling
Applicable safety standards EN62040-1-1:2003 IEC60950-1:2001
Electromagnetic compatibility EN62040-2:2006
Acoustic noise ≤55DB
Others
Cabinet Standard 19 inch cabinet
Monitor management system UPSupervisor
Interface RS232, RS485 and 8 try contact, TCP/IP adapter, SNMP(optional)
Display Touch LCD/LED Screen