AWM 3642 Fiberglass Braid Silicone Insulated Motor Connection Wire
Conductor: Bare copper, tinned copper
Insulator: Silicone rubber
Jacket: Synthetic yarn braiding with silicone resin coating
Rated temp: 150/180℃
Rated volt: 6900V
Test voltage: 14.8KV. 1min
Flame test: FT 2
Application
AWM 3642 fiberglass braid silicone insulated motor connection wire is used where high flexibility is required and high temperature conditions. It is therefore a suitable connection cable for home electric appliance, high voltage machines like transformers, generators, motors, traction machines.
AWG NO. | Conductor | Insulation thickness | Braiding thickness | Cable OD | Resistance Ω/KM Max. | ||||
Size | Structure | OD | Nominal | OD | Nominal | Tolerance | |||
mm² | No./mm | mm | mm | mm | mm | mm | mm | ||
16 | 1.31 | 7/0.49 | 1.55 | 2.2 | 5.95 | 0.20 | 6.40 | +0.30-0.20 | 14.6 |
26/0.254 | |||||||||
52/0.18 | |||||||||
15 | 1.65 | 33/0.254 | 1.75 | 2.2 | 6.15 | 0.20 | 6.60 | +0.30-0.20 | 11.3 |
14 | 2.08 | 41/0.254 | 1.95 | 2.2 | 6.35 | 0.2 | 6.80 | +0.30-0.20 | 8.96 |
7/0.62 | |||||||||
37/0.26 | |||||||||
13 | 2.63 | 52/0.254 | 2.15 | 2.2 | 6.55 | 0.20 | 7.00 | +0.30-0.20 | 7.10 |
12 | 3.31 | 65/0.254 | 2.5 | 2.2 | 6.9 | 0.20 | 7.30 | +0.30-0.20 | 5.64 |
43/0.32 | |||||||||
11 | 4.17 | 83/0.254 | 2.74 | 2.2 | 7.14 | 0.25 | 7.70 | +0.30-0.20 | 4.48 |
34/0.40 | |||||||||
10 | 5.261 | 35/0.45 | 3.20 | 2.2 | 7.60 | 0.25 | 8.10 | +0.30-0.20 | 3.55 |
9 | 6.631 | 53/0.40 | 3.98 | 2.2 | 8.38 | 0.25 | 8.90 | +0.30-0.20 | 2.81 |
8 | 8.367 | 70/0.40 | 4.40 | 2.2 | 8.80 | 0.25 | 9.30 | +0.30-0.20 | 2.30 |
7 | 10.55 | 84/0.40 | 4.60 | 2.2 | 9.00 | 0.30 | 9.60 | +0.30-0.20 | 1.79 |
6 | 13.30 | 105/0.40 | 5.30 | 2.2 | 9.70 | 0.30 | 10.3 | +0.40-0.20 | 1.42 |
5 | 16.77 | 133/0.40 | 6.00 | 2.2 | 10.4 | 0.30 | 11.0 | +0.40-0.20 | 1.12 |
4 | 21.15 | 168/0.40 | 6.80 | 2.2 | 11.2 | 0.30 | 11.8 | +0.40-0.20 | 0.89 |
3 | 26.67 | 210/0.40 | 7.60 | 2.2 | 12.0 | 0.55 | 13.1 | +0.40-0.20 | 0.707 |
2 | 33.62 | 268/0.40 | 8.50 | 2.2 | 12.5 | 0.55 | 13.6 | +0.40-0.20 | 0.56 |
1 | 42.41 | 217/0.50 | 9.60 | 2.2 | 14.0 | 0.55 | 15.1 | +0.40-0.20 | 0.449 |
1/0 | 53.49 | 276/0.50 | 11.2 | 2.2 | 15.6 | 0.55 | 16.7 | +0.40-0.20 | 0.355 |
2/0 | 67.43 | 342/0.50 | 12.2 | 2.2 | 16.6 | 0.55 | 17.7 | +0.40-0.20 | 0.282 |
3/0 | 85.01 | 437/0.50 | 13.8 | 2.2 | 18.2 | 0.65 | 19.3 | +0.40-0.20 | 0.223 |
4/0 | 107.2 | 551/0.50 | 15.5 | 2.2 | 19.9 | 0.65 | 21.0 | +1.0 -0.50 | 0.177 |
250kcmil | 127.0 | 646/0.50 | 17.5 | 2.2 | 21.9 | 0.65 | 23.0 | +1.0 -0.50 | 0.151 |
300kcmil | 152.0 | 779/0.50 | 19.5 | 2.2 | 23.9 | 0.65 | 25.0 | +1.0 -0.50 | 0.125 |
350kcmil | 177.0 | 912/0.50 | 21.0 | 2.2 | 25.4 | 0.65 | 26.5 | +1.0 -0.50 | 0.108 |
400kcmil | 203.0 | 1036/0.50 | 23.0 | 2.2 | 27.7 | 0.65 | 28.8 | +1.0 -0.50 | 0.0942 |
Mechanical Properties
Tensile strength: ≥3.45N/mm²
Elongation at break of insulation: ≥100%
Min. bending radius: 6×OD
Standard: UL758, UL62, UL1581
Characteristics
AWM 3642 fiberglass braid silicone insulated motor connection wire has very good flexibility and good performance of resistance to high temperature, ranging from -55℃ up to 180℃.
The use of silicone rubber, a high grade corona resistant insulation material, gives the cable excellent dielectric strength.
The braided synthetic yarn covering, which is applied directly over the insulation, gives the cable, because of its short braiding pitch and high compactness, an excellent mechanical protection by maintaining good flexibility.
The varnishing of the braiding results in good antifriction properties, high abrasion resistance and excellent chemical resistance against transformer oil, light fuel oil and most types of cleaning agents.
In the event of fire, no corrosive and toxic gases will be given off.
Hence, damage caused by fire can be kept to minimum.