FRP Crossflow Cooling Tower (Low Noise)

FRP Crossflow Cooling Tower (Low Noise)

The FRP crossflow cooling tower features a low noise, with the lowest noise level at only 59.5dB. This makes it ideal for use in environments with strict requirements on noise levels, such as business and residential buildings. This series of evaporative cooling systems are available in a number of models, and customers can choose the right cooling tower system depending on their needed circulating water flow. Users can also choose by noise degree, which is listed in the following standard product details. We also offer non-standard designs according to specific customer requirements.

Design condition
  • Inlet water temperature: T1=37℃
  • Outlet water temperature: T2=32℃
  • Wet bulb temperature: TWB=28℃
  • Dry bulb temperature: T=31.8℃
  • Atmospheric pressure: P=9.94×104 Pa
Selection table of low noise type crossflow cooling towers
Model Overall dimension Cooling Flow rate (m3/h) Fan φ(mm) Motor (HP) Weight (Kg) Noise (dB)
L W H Tower body H1 Fan cylinder H2 Dry Wet
LRT-100L/S 1970 3300 3700 2300 700 100 1470 2 995 1610 58.5
LRT-125L/S 2360 3600 3700 2300 700 125 1800 5 1100 2620 59.5
LRT-150L/S 2650 3900 3700 2300 700 150 2100 5 1230 2830 60.5
LRT-175L/S 2650 3900 3700 2300 700 175 2100 7.5 1350 3150 60.5
LRT-200L/S 3090 4300 3700 2300 700 200 2400 7.5 1490 3580 61.5
LRT-225L/S 2900 4990 4080 2680 700 225 2400 7.5 1650 3740 61.5
LRT-250L/S 3150 4990 4080 2680 700 250 2400 10 2320 4520 62
LRT-300L/S 3500 5590 4080 2680 700 300 3000 15 2520 5580 62.5
LRT-350L/S 3600 5590 4080 2680 700 350 3000 15 2790 5920 63
LRT-400L/S 3840 5930 4230 2680 850 400 3330 15 3190 6630 63.5
LRT-450L/S 4090 5930 4230 2680 850 450 3330 20 3600 7290 63.8
LRT-500L/S 4350 6080 4850 3300 850 500 3330 20 4200 8150 64.2
LRT-600L/S 4650 6400 4850 3300 850 600 3700 25 4620 8960 65
LRT-700L/S 4950 6400 5450 3900 850 700 3700 30 5040 9610 66.5
LRT-800L/S 5250 6900 5500 3900 900 800 4200 30 5620 10710 67

Note:
1. Listed above are the technical parameters of a single fan cooling tower. Each model can be used individually or as part of a combination system.
2. The cooling tower head is almost equal to H- the tower height.

Related products
Send Message