Packaged Rooftop Air Conditioner
Our packaged rooftop air conditioner can be mounted on a rooftop. Powerful and reliable, this rooftop aircon has several advantages for handling both demanding and light commercial applications.
Features of Packaged Rooftop Air Conditioner
We carefully select all our raw materials from reliable suppliers and design this commercial air conditioner to comply with international industry standards for use in a wide range of commercial applications.
1. High static pressure of air supply;
2. Continuous fresh airflow enhancing the indoor air quality;
3. High-efficiency evaporator cooling the air directly;
4. High operation efficiency, energy efficiency, great reliability and low noise;
5. Wide application range from mid-sized stores to cinemas and shopping malls to office buildings and factories and other public places.
Technical Specifications of Packaged Rooftop Air Conditioner
Part No. | Cooling Capacity (kW) | Heating Capacity (kW) | Rated Airflow (m3/h) | External Static Pressure (Pa) | Input Power (kW) | Noise dB(A) | Charge Of R22 (kg) | Dimension | Weight (kg) | ||
Length (mm) | Width (mm) | Height (mm) | |||||||||
7.8 | 7.8 | 1700 | 180 | 3.1 | 66 | 2.8 | 1104 | 954 | 780 | 198 | |
9.1 | 9.4 | 2000 | 220 | 3.3 | 66 | 3.2 | 1104 | 954 | 780 | 198 | |
11.5 | 12.1 | 2500 | 250 | 4.6 | 66 | 3.6 | 1160 | 1050 | 845 | 210 | |
14.3 | 14.2 | 3000 | 250 | 5.2 | 68 | 4.6 | 1360 | 1190 | 865 | 238 | |
17.1 | 18 | 3600 | 250 | 6.4 | 68 | 5.0 | 1360 | 1190 | 865 | 246 | |
19.9 | 19.5 | 4000 | 300 | 7.2 | 68 | 5.8 | 1650 | 1170 | 865 | 362 | |
24.2 | 24.5 | 5000 | 300 | 8.9 | 70 | 7.2 | 1650 | 1560 | 860 | 423 | |
30.6 | 30.6 | 6500 | 300 | 11.0 | 70 | 8.0 | 1800 | 1800 | 1010 | 500 | |
34.8 | 32.4 | 7200 | 350 | 12.0 | 70 | 8.4 | 1800 | 1800 | 1010 | 528 | |
39.7 | 36.1 | 7900 | 350 | 13.3 | 70 | 8.8 | 2100 | 1850 | 1305 | 622 | |
44.6 | 44.2 | 970 | 350 | 15.3 | 72 | 11.2 | 2300 | 1850 | 1305 | 632 | |
48.6 | 44.2 | 10080 | 400 | 19.2 | 72 | 14.4 | 2500 | 1850 | 1450 | 780 | |
55.6 | 57.4 | 10800 | 400 | 20.6 | 72 | 14.8 | 2500 | 1850 | 1450 | 800 | |
65.5 | 60.7 | 12600 | 400 | 23.1 | 72 | 18.8 | 2550 | 2100 | 1580 | 850 | |
72.8 | 66.6 | 14000 | 400 | 25.4 | 72 | 18.8 | 2600 | 2130 | 1580 | 915 | |
80.4 | 80.7 | 15500 | 450 | 29.9 | 74 | 19.6 | 2600 | 2130 | 1580 | 970 | |
88.5 | 85.1 | 17280 | 450 | 33.9 | 74 | 21.6 | 3100 | 2130 | 1880 | 1140 | |
102.2 | 98.5 | 19800 | 450 | 40.9 | 74 | 22.4 | 4000 | 2050 | 1950 | 1700 | |
117.6 | 116.2 | 23400 | 450 | 48.1 | 74 | 29.2 | 4100 | 2050 | 2050 | 1860 | |
137.8 | 132.0 | 27000 | 450 | 57.2 | 76 | 30.0 | 4200 | 2050 | 2050 | 2120 | |
156.2 | 152.5 | 30600 | 500 | 65.2 | 76 | 37.6 | 4200 | 2050 | 2050 | 2120 | |
176.8 | 169.4 | 34200 | 500 | 75.4 | 78 | 39.2 | 4200 | 2150 | 2350 | 2360 | |
201.8 | 196.2 | 37800 | 550 | 85.8 | 78 | 48.0 | 4200 | 2200 | 2350 | 2570 |
Please note that
1. Nominal Condition for Cooling: air inlet temperature 27℃ (DB)/19℃ (WB), ambient temperature: 35℃ ;
2. Nominal Condition for Heating: air inlet temperature 20℃ , ambient temperature: 7℃ .