Pad-mounted Transformer

Pad-mounted Transformer
Pad-mounted Transformer
Pad-mounted Transformer

Pad-mounted transformers, also known as American substations, are an integrated power station that combines high-voltage control, protection, transformers and power distribution equipment according to specific wiring requirements. Transformer bodies, high load breaking switches and fuses are all set in fully sealed transformer oil tanks, and the transformer oil features an outstanding insulation performance and heat dissipation performance. Pad-mounted transformers feature a small size and light weight, as well as a safe, convenient installation and maintenance. They are widely used for outdoor power supply in cities, residential areas, hospitals, factories, mines, airports and railways.

Working conditions
  • Altitude: ≤1000m
  • Wind speed: ≤35m/S (≤700pa)
  • Ambient temperature: -35ºC - +40ºC
  • Relative humidity: daily average humidity≤95%, monthly average humidity≤95%
  • Quakeproof: horizontal acceleration≤0.4m/s2
  • vertical acceleration≤0.15mm/s2
  • Installation site slop: ≤3º
  • Installation site: the place without fire and explosion danger, serious pollution, chemical corrosion and strenuous vibration
Features
  • Small size and compact structure. The area covered is only 1/3 to 1/5 that of European substations of the same capacity.
  • Low noise and strong overload capacity S11 series transformers: The system includes high-voltage chambers, low voltage chambers, and transformers. The high voltage components feature fuse protection and are used for loop networks and terminals. Power supply methods are also flexible.
  • High-voltage chambers are equipped with oil humidity gauges, oil level gauges, pressure relief valves and oil discharging valves to monitor transformer operation states.
  • High voltage inlets use cable plugs and can be equipped with zinc oxide arresters. We will meet your needs for a variety of low voltage outputs and low voltage measurements, with shunt outlets added according to customer requirements.
  • The transformers utilize corrugated plates for heat dissipation. These plates are treated using a special technology for an exceptional corrosion resistance and a variety of shapes and structures. Common plates and stainless-steel plates can be chosen according to your needs.
Technical parameters
Model Rated capacity
(KVA)
Voltage and tapping link range
High voltage(KV)
Voltage and tapping link range
Tapping link range(%)
Voltage and tapping link range
Low voltage(KV)
Connection and vector group No-load losses(W) Load losses(W) No-load current(%) Short circuit impedance(%) Dimensions
L×W×H (mm)
ZGS11-100 100 6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4 Yyn0
Dyn11
200 1580/1500 1.8 4 11830x1355x1735
ZGS11-125 125 240 1890/1800 1.7 1830x1365x1735
ZGS11-160 160 270 2310/2200 1.6 1830x1375x1735
ZGS11-200 200 340 2730/2600 1.5 1830x1375x1735
ZGS11-250 250 400 3200/3050 1.4 1830x1405x1735
ZGS11-315 315 480 3830/3650 1.4 1830x1425x1735
ZGS11-400 400 570 4520/4300 1.3 1830x1435x1805
ZGS11-500 500 680 5410/5150 1.2 1830x1445x1860
ZGS11-630 630 810 6200 1.1 4.5 1830x1445x1860
ZGS11-800 800 980 7500 1 1830x1490x1860
ZGS11-1000 1000 1150 10300 1 1830x1675x2005
ZGS11-1250 1250 1360 12000 0.9 2100x1845x2035
ZGS11-1600 1600 1640 14500 0.8 2100x1885x2135