H05RN-F Multicore Rubber Insulated Power Cable

H05RN-F Multicore Rubber Insulated Power Cable
H05RN-F Multicore Rubber Insulated Power Cable

Conductor: Bare copper, tinned copper
Insulator: EPR rubber
Jacket: CPE rubber
Rated volt.: 300/500V, 450/750V
Test voltage: 2000V. 5Min
Rated temp.: -30℃~ 70℃

Application
Rubber insulated power cable is popularly used in locomotive equipment, electric motor, marine cable, mineral, underwater, welding machines etc.

Technical Parameters
Core×Size Construction Insulation Jacket thickness Cable OD Resistance Ω/KM
Thickness OD Nominal Toler.
mm² No./Dia (mm) mm mm mm mm mm Max.
2×0.5 16/0.20 0.6 2.15 0.8 5.9 ±0.20 40.1
3×0.5 16/0.20 0.6 2.15 0.8 6.2 ±0.20 40.1
4×0.5 16/0.20 0.6 2.15 0.8 6.8 ±0.25 40.1
5×0.5 16/0.20 0.6 2.15 0.8 7.4 ±0.30 40.1
2×0.75 24/0.20 0.6 2.35 0.8 6.3 ±0.20 26.7
3×0.75 24/0.20 0.6 2.35 1.0 7.1 ±0.25 26.7
4×0.75 24/0.20 0.6 2.35 1.0 7.7 ±0.30 26.7
5×0.75 24/0.20 0.6 2.35 1.0 8.4 ±0.30 26.7
2×1.0 32/0.20 0.6 2.55 1.0 7.1 ±0.25 20.0
3×1.0 32/0.20 0.6 2.55 1.0 7.5 ±0.30 20.0
4×1.0 32/0.20 0.6 2.55 1.0 8.2 ±0.30 20.0
5×1.0 32/0.20 0.6 2.55 1.0 8.9 ±0.30 20.0
2×1.5 30/0.25 0.6 2.90 1.0 7.8 ±0.30 13.7
3×1.5 30/0.25 0.6 2.90 1.0 8.3 ±0.30 13.7
4×1.5 30/0.25 0.6 2.90 1.0 9.0 ±0.30 13.7
5×1.5 30/0.25 0.6 2.90 1.1 10.0 ±0.30 13.7

Mechanical Properties
Insulator physical performance
Tensile strength: ≥5N/mm2
Elongation at break of insulation: ≥250%
Jacket physical performance
Tensile strength: ≥7N/mm2
Elongation at break of insulation: ≥300%
Min.Bending radius: 7×OD
Standards: IEC60332-1, IEC60228, VDE 0293

Characteristics
Rubber cable has good performance, including low hardness, good flexibility, high tear strength, flame retardant performance, thermal stability. It can bear the temperature from -30℃ ~ 70℃. It’s also anti-UV and anti-ozone.