European Standard Magnetic HID Ballast
EuropeanStandard Magnetic HID Ballast
The European standardmagnetic HID ballast is applicable for commercial lighting system, outdoorlighting system and other places where high brightness is required. This product is cheap, but itcould offer stable performance for quite a long time. In addition, itshould work together with capacitor and trigger.
Technical Parameters
Model | Input voltage | Dimensions | Lamp power | Lamp voltage | Lamp current | Start current | Line current | Shunt capacitor | Temperature Rise | Operating temperature | Wiring diagram | |||
A | B | C | D | |||||||||||
RSB35SML | 220-230VAC, 50Hz | 117 | 93 | 60 | 51.5 | 35W | 85V | 0.53A | ≤0.267A | 0.213A | 6μF | ≤70K | ≤110°C | A |
RSB50MYL | 220-230VAC, 50Hz | 117 | 93 | 60 | 51.5 | 50W | 95V | 0.62A | ≤0.407A | 0.285A | 6μF | ≤70K | ≤110°C | A |
RSB70SML | 220-230VAC, 50Hz | 117 | 93 | 60 | 51.5 | 70W | 90V | 0.98A | ≤0.511 A | 0.402A | 12μF | ≤70K | ≤110°C | A |
RSB100MYL | 220-230VAC, 50Hz | 117 | 93 | 60 | 51.5 | 100W | 100V | 1.10A | ≤0.752A | 0.550A | 12μF | ≤70K | ≤110°C | A |
RSB150SML | 220-230VAC, 50Hz | 125 | 102 | 75 | 64 | 150W | 100V | 1.8A | ≤1.160A | 0.810A | 18μF | ≤70K | ≤110°C | A |
RSB175MYL | 220-230VAC, 50Hz | 125 | 102 | 75 | 64 | 175W | 130V | 1.5A | ≤1.660A | 0.920A | 12μF | ≤70K | ≤110°C | A |
RSB250MYL | 220-230VAC, 50Hz | 125 | 102 | 75 | 64 | 250W | 130V | 2.13A | ≤2.180A | 0.132A | 18μF | ≤70K | ≤110°C | A |
RSB250SML | 220-230VAC, 50Hz | 150 | 127 | 75 | 64 | 250W | 100V | 3.00A | ≤1.180A | 1.400A | 32μF | ≤70K | ≤110°C | A |
RSB400MYL | 220-230VAC, 50Hz | 150 |