Earthing Switch (JN15 Indoor High Voltage Earthing Switch)

Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
Earthing Switch <small>(JN15 Indoor High Voltage Earthing Switch)</small>
  • JN15-12 Earthing Switches
  • JN15-24 Earthing Switches
  • JN15-40.5 Earthing Switches

Introduction
The JN15 earthing switch is our world-advanced new development designed in reference to the EK6 earthing switch of German GALOR-EMAG company. It has advantages of cutting-edge design, reliable performance, simple structure and ease of mounting and commissioning. The performance not only meets GB1985-2004 requirements, but also complies with German DINVDE670 and IEC129 standards. As a type of electrical components, the indoor high voltage earthing switch works with ABB-UniGear ZS1, ZS2, Siemens-NXAIR, Schneider-Nvnex and Tellhow-KYN28A type medium voltage switchgear.

Service Conditions
1) Altitude: ≤1000m
2) Ambient air temperature: up to 40 ℃, down to -10 ℃, daily range of 15 ℃
3) Humidity: daily average relative humidity less than 95%; monthly average relative humidity less than 90%
4) Earthquake intensity: ≤ 8 degrees

Model and Meaning
1. □- Pole-center distance
2. □- Rated short time withstand current (KA)
3. □- Rated voltage (KV)
4. 15 - Design number
5. N-Indoor
6. J-Earthing switch
Technical Parameters
Rated voltage (KV)12 24 40.5
Rated short time withstand current (KA)31.5, 40, 50 31.5 31.5
Rated short circuit duration (S) 4 4 4
Rated peak withstand current (KA)80, 100, 125 80 80
Rated short-circuit making current (KA)80, 100, 125 80 80
Pole-center distance (mm) 165,180,200,210,220,230,250,275 210,265,275 280,300,350,400,440
Rated 1min power frequency withstand voltage (KV)42 65 95
Rated lightning impulse withstand voltage (KV)75 125 185
Mechanical life (cycles)2000 2000 2000

Outline and Mounting Dimension

JN15-12 Earthing Switches
JN15-24 Earthing Switches
JN15-40.5 Earthing Switches